MV Switchboards

A. SYMATICPlus Air insulated Compact metal clad Switchgears up to 12KV with vacuum circuit breaker On withdraw able truck.

  • Earthed Metallic Partitions & Shutters
  • Compact Metal clad design & type tested design as per IEC 60298, IS 3427 & IEC 60694 IS 12729 & IEC 62271-200
  • VCB mounted on a Drawout truck
  • Siemens VCB having imported Siemens vacuum interrupter with high reliability
  • All operations including rack in & rack out and mechanical on/off are possible with door closed.
  • Dimensions are 600mm (W) x 2300mm (H) x 1350mm (D)




B. Outdoor VCB panel up to 36KV

  • Metal clad design & VCB mounted on fixed/Drawout truck. No separate trolley for maintenance required. safe and easy Truck movement behind closed cubicle door.
  • Independent pad lockable shutter for bus and cable side, Automatic dropping ramp to facilitate truck removal.
  • Safe and easy lifting arrangement & type tested design as per IEC 60298, IS 3427 & IEC 60694 IS 12729 / IP 55. 12KV up to 40KA & 36KV up to 31.5KA
  • The outdoor panel is equipped with a Top slanted roof under which an additional internal ceiling is fixed, the external & internal ceiling are separated by a volume of air. This air plays a remarkable role in insulating the internal equipment of the Outdoor panel from the external heating sources. (Mainly due to sun radiations).
  • The outdoor panels are designed and fabricated using materials and equipment capable of withstanding harsh climatic and Operational conditions.
  • Dimensions for 12KV are 600/800mm (W) x 2300mm (H) x 1350/1750mm (D) & 36KV 1100 x 2500 x 2700mm.




LV Switchboards

  • It is Metal clad type & having totally type tested design up to 6300A 415V AC 50/60Hz.
  • It as per ICE 61439 Part – I & II and IS 8623 & IS 2147
  • Having type test certificates for 65KA 1 second and IP 43 for ACB feeder & IP 54/55 for MCC and others.
  • The LV switchboards are designed in fixed and Drawout both type where the MCC are up to 4000A and PCC are up to 6300A.
  • It can be delivered in two different way of structures, one is our owned symatic design having wide cable alley & vertical bus chamber and another one compact design of SIEPAN 8PU under technical collaboration & guidelines of Siemens Ld.
  • All the bought out items are purchased directly from reputed manufacturers & suppliers to meet the quality norms.

LV Busducts

  • It is Metal clad type & having type tested design up to 6300A 415V AC 50/60Hz.
  • Having type test certificates for 65KA 1 second and 50KA 3 seconds.
  • Totally insulated live parts and having good heat dissipation capacity for particular current & voltage ratings.
  • It is having parallel earthing path to avoid shock & hazardous to operators due to leakage currents or instant of any fault conditions.
  • Having provision for space heater & Silica gel to absorb moisture during raining season or when not in use.

Control Desks

  • It is Metal clad type & having type tested design suitable for PLC/SCADA/DCS system & remote operations along with fault annunciation for motor control & power control panel.

Control & Relay Panels

  • It is Metal clad type & having type tested design suitable up to 400KV switchyards
  • It is equipped with Siemens, Areva & CSPC protective relays along with MIMIC presentation.

Packing Procedure of Busducts

  • Busducts packing through wooden box Wrapped with plastic.